Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/19/2009

Applicant:

ALLIED TRADING & TRANSACTING CORP NV 61.16%

Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T09FR02707
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
08/19/2009 INSP - FULL NSPRENGE Violation The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). 1.__Problem: There is an extension cord connected to one of your cold tables. TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. CORRECTION: You will remove the extension cord from use. 2.__Problem: There is no copy of your Commercial Cooking Suppression System/hood system inspection on premises. There is no copy of the last Hood system cleaining. Problem: IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. Problem: IFC 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. CORRECTION: You will maintain records of your hood inspections/cleanings on the premises and provide to the fire marshal upon re-inspection. The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated. Property Representative Signature: _________________________. Fire Inspector Signature: _________________________(791-4502). Reinspection Date: ___/___/___ or later. ___Approved ___Not Approved