Description:

Full Inspection conducted 7/31/09 I have received a copy of this report and understand the corrections needed: ________________ Business Owner: Johnny Murray, Phone: 745-4529 Inspector: __________________, Captain: _____________ David Greenleaf, MA 23 If you have any questions please call 791-4502. Approved: ________ Re-inspection: __/__/__ (or after)

Outstanding Inspections

Case Number: T09FR02697
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
07/31/2009 INSP - FULL DGREENLE Violation Certificate of Occupancy: POSTED - Type: S-1 Please correct the following violations of the Tucson fire code: TFC 605.5 - Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring…. Extension cords shall be used only with portable appliances. _____ Soda Machine _____ DVD player _____ Fan, rear of store _____ Microwave in shop TFC 2703.5 - Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. _____ "Corrosives" at gate near used batteries _____ "Flammable" above parts cleaner and parts cleaner barrel storage 2703.7.1 - Smoking. Smoking shall be prohibited and "No Smoking" signs provided as follows: 2. Within 25 feet of outdoor storage, dispensing or open use areas. 3. Facilities or areas within facilities that have been designated as totally "no smoking" shall have "No Smoking" signs placed at all entrances to the facility or area. Designated areas within such facilities where smoking is permitted either permanently or temporarily, shall be identified with signs designating that smoking is permitted in these areas only. 4. In rooms or areas where flammable or combustible hazardous materials are stored, dispensed or used. _____ Post "No Smoking" signs in shop and storage yard north of shop TFC 105.6.16 - Flammable and combustible liquids. An operational permit is required: 3. To store, handle or use Class II, Class IIIA or Class IIIB …in excess of 60 gallons … _____ Obtain permits for above-ground storage tanks (AST)'s To apply for a permit you must provide a floor plan (or plot plan) indicating the location of storage tanks and their contents. Tanks will need to be equipped with emergency vents and labeled prior to approval. TFC 2703.2.2.1 - Design and construction. Piping, tubing, valves, fittings and related components used for hazardous materials shall be in accordance with the following: 1. Piping, tubing, valves, fittings and related components shall be designed and fabricated from materials that are compatible with the material to be contained and shall be of adequate strength and durability to withstand the pressure, structural and seismic stress and exposure to which they are subject _____ Replace or relocate plastic Intermediate Bulk Container (IBC) which is not designed for prolonged exposure to sun. TFC 107.1 - Maintenance of safeguards. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards. _____ Maintain East door (behind desk) in an operative condition or remove hardware and label "Door Blocked" on both sides (if visible). TFC 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use… _____ Clear shop exterior doorway (egress side and discharge side). TFC 605.3 - Working space and clearance. A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear tires and used batteries from directly in front of electrical service panels. TFC 906.5 - Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. TFC 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 shall be installed so that its top is not more than 5 feet above the floor…The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches. _____ Mount extinguishers in an approved manner
10/13/2009 INSP - REINSPECTION DGREENLE Partial Approval done except for tank permits