Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/13/2009

Applicant:

BREWSTER FAMILY TR (THE)

Description:

Full Fire Prevention Inspection

Outstanding Inspections

Case Number: T09FR02669
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
08/13/2009 VIOL - PRECAUTION AGAINST FIRE DSIWARSKI Violation IFC.308.2 Where prohibited. A person shall not take or utilize an open flame or light in a structure, vessel, boat or other place where highly flammable, combustible or explosive material is utilized or stored. Lighting appliances shall be well-secured in a glass globe and wire mesh cage or a similar approved device. ____Fire place shall be placed out of service until in compliance with building codes.
08/13/2009 VIOL - BUILDING SVCS & SYSTEMS DSIWARSKI Violation IFC.05.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ____Open wireing shall be prohibited. Covers are required on all electrical boxes in Room 4, Room 3, Library and all other rooms.
08/13/2009 VIOL - BUILDING SVCS & SYSTEMS DSIWARSKI Violation IFC.605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. ____Room #6 Exposed electrical wireing shall be encased. ____Exhaust fan in kitchen the permanent wireing shall be encased. ____Master bath room permanent wiring needs to be encased.
08/13/2009 VIOL - BUILDING SVCS & SYSTEMS DSIWARSKI Violation IFC.605.4.1 Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. ____Room 5 Relocatable power tap will be required.
08/13/2009 VIOL - BUILDING SVCS & SYSTEMS DSIWARSKI Violation IFC.605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Relocatable power shall not be pluged into electrical receptacle with extension card in kitchen and room 5.
08/13/2009 VIOL - FIRE PROTECTION SYSTEMS DSIWARSKI Violation IFC.901.6.1 Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed in Table 901.6.1. ____Sprinkler System shall be tested per NFPA 25. ____The five (5) year check valve test is required.
08/13/2009 VIOL - FIRE PROTECTION SYSTEMS DSIWARSKI Violation IFC.906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Portable fire extinguisher shall be serviced maintained.
08/13/2009 VIOL - FIRE PROTECTION SYSTEMS DSIWARSKI Violation

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02669
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/13/2009 VIOL - MEANS OF EGRESS DSIWARSKI Approved IFC.901.6.1 Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed in Table 901.6.1. IBC.1109.13 Number 7. ____Pool gate must be replaced with a single thumb turn lock.