Case: T09FR02646
Case Details
Entered Date:
08/11/2009
Applicant:
RIVERFRONT VILLAGE JIB LLC
Description:
Full Fire Prevention Inspection. Alina Esquibel...888-8846
Outstanding Inspections
Case Number: T09FR02646
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/11/2009 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | IFC 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. _____1. Address numbers shall be in accordance with Pima County address display requirements. NOTE: See attached requirements. |
| 08/11/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request. _____ 1. Provide the hood system and fire extinguisher inspection reports. |
| 08/11/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____ 1. Repair the emergency lighting unit located on the wall by the registers. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02646
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |