Case: T09FR02644
Case Details
Entered Date:
08/10/2009
Applicant:
BROADWAY-KOLB LLC
Description:
Initial inspection 8/10/09
Outstanding Inspections
Case Number: T09FR02644
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2009 | VIOL - ADMINISTRATION | MPURSLEY | Correction Required | 105.6.16 Flammable and combustible liquids. An operational permit is required to store, handle or use Class II or Class IIIA liquids in excess of 25 gallons (95 L) in a building or in excess of 60 gallons (227 L) outside a building, except for fuel oil used in connection with oil-burning equipment. _____Have tanks permitted. |
| 08/10/2009 | VIOL - FLAMMABLE LIQUIDS | MPURSLEY | Correction Required | 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. Emergency vents for Class I, II and IIIA liquids shall not discharge inside buildings. The venting shall be installed and maintained in accordance with Section 4.2.5.2 of NFPA 30. _____Have tanks properly vented. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02644
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2009 | INSP - REINSPECTION | MPURSLEY | Approved | All corrections made; turned over to Corrales for permit. |