Case: T09FR02639
Case Details
Entered Date:
08/10/2009
Applicant:
EL CAMPO PROPERTIES LLLP
Description:
Meineke Sheldon Stannard 520-298-5500 Inspector M. Pursley
Outstanding Inspections
Case Number: T09FR02639
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2009 | VIOL - ADMINISTRATION | MPURSLEY | Correction Required | 105.6.16 Flammable and combustible liquids. An operational permit is required to store, handle or use Class II, IIIA, or IIIB liquids in excess of 25 gallons (95 L) in a building or in excess of 60 gallons (227 L) outside a building, except for fuel oil used in connection with oil-burning equipment. _____Have tanks permitted. |
| 08/10/2009 | VIOL - BUILDING SVCS & SYSTEMS | MPURSLEY | Correction Required | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used… Electrical blanks shall be placed in all open spaces within any electrical panel or box. _____ Place electrical blanks in any open void spaces in your electrical panel |
| 08/10/2009 | VIOL - FIRE RESIST.RATED CONST | MPURSLEY | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix and repair all openings or holes in the ceiling |
| 08/10/2009 | VIOL - MEANS OF EGRESS | MPURSLEY | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the pad lock and replace with an approved locking device such as, thumb turn lock or panic hardware |
| 08/10/2009 | VIOL - WELDING & OTHER HOT WRK | MPURSLEY | Correction Required | 2604.2.6 Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum 2-A:20-B:C rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed. _____Have appropriate fire extinguishers mounted properly. |
| 08/10/2009 | VIOL - FLAMMABLE LIQUIDS | MPURSLEY | Correction Required | 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. Emergency vents for Class I, II and IIIA liquids shall not discharge inside buildings. The venting shall be installed and maintained in accordance with Section 4.2.5.2 of NFPA 30. _____Have tanks properly vented. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02639
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2009 | INSP - REINSPECTION | MPURSLEY | Approved | All corrections made;turned over to Corrales for tank permits. |