Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/10/2009

Applicant:

EL CAMPO PROPERTIES LLLP

Description:

Meineke Sheldon Stannard 520-298-5500 Inspector M. Pursley

Outstanding Inspections

Case Number: T09FR02639
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
08/10/2009 VIOL - ADMINISTRATION MPURSLEY Correction Required 105.6.16 Flammable and combustible liquids. An operational permit is required to store, handle or use Class II, IIIA, or IIIB liquids in excess of 25 gallons (95 L) in a building or in excess of 60 gallons (227 L) outside a building, except for fuel oil used in connection with oil-burning equipment. _____Have tanks permitted.
08/10/2009 VIOL - BUILDING SVCS & SYSTEMS MPURSLEY Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used… Electrical blanks shall be placed in all open spaces within any electrical panel or box. _____ Place electrical blanks in any open void spaces in your electrical panel
08/10/2009 VIOL - FIRE RESIST.RATED CONST MPURSLEY Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix and repair all openings or holes in the ceiling
08/10/2009 VIOL - MEANS OF EGRESS MPURSLEY Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the pad lock and replace with an approved locking device such as, thumb turn lock or panic hardware
08/10/2009 VIOL - WELDING & OTHER HOT WRK MPURSLEY Correction Required 2604.2.6 Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum 2-A:20-B:C rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed. _____Have appropriate fire extinguishers mounted properly.
08/10/2009 VIOL - FLAMMABLE LIQUIDS MPURSLEY Correction Required 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. Emergency vents for Class I, II and IIIA liquids shall not discharge inside buildings. The venting shall be installed and maintained in accordance with Section 4.2.5.2 of NFPA 30. _____Have tanks properly vented.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02639
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/09/2009 INSP - REINSPECTION MPURSLEY Approved All corrections made;turned over to Corrales for tank permits.