Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/05/2009

Applicant:

LOS TRES ABOGADOS LLC

Description:

Full Fire Prevention Inspection

Outstanding Inspections

Case Number: T09FR02616
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
08/05/2009 VIOL - BUILDING SVCS & SYSTEMS DSIWARSKI Violation IFC.605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. ____Blank required in electrical service panel in the scan room.
08/06/2009 VIOL - FIRE RESIST.RATED CONST DSIWARSKI Violation IFC.703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated.... ____Sprinkler head in record room needs to be sealed.
08/06/2009 VIOL - FIRE PROTECTION SYSTEMS DSIWARSKI Violation IFC.901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Inspection and testing of sprinkler systems shall be in compliance with NFPA 25. ____The five (5) year check valve test/inspection is required.
08/06/2009 VIOL - FIRE PROTECTION SYSTEMS DSIWARSKI Violation IFC.906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Portable fire extinguisher needs to be serviced/maintained.
08/06/2009 VIOL - MEANS OF EGRESS DSIWARSKI Violation IFC.1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. ____Emergency lighting by front and back door needs to be serviced/maintained.