Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/04/2009

Applicant:

UNREIN INVESTMENTS LLC

Description:

Full fire prevention inspection. Jack Finley 622-1622

Outstanding Inspections

Case Number: T09FR02586
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
08/04/2009 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required IFC 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property _____1. Address numbers shall be in accordance with Pima County address display requirements. NOTE: See attached requirements.
08/04/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____1. Remove all cube adapters located in the office. NOTE: Replace them with a fused power-strip.
08/04/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove all storage from obstructing the electrical equipment located in the stock room.
08/04/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1. Remove the extension cord used to power the fan located on the southwest corner shelf. NOTE: Replace it with a fused power-strip.
08/04/2009 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. _____1. Replace the damaged ceiling tile located above the east exit door.
08/04/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. Test all exit signs for emergency back-up power and repair any deficencies. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02586
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/19/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.