Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02564
Case Description: INSPECTION
Total Completed Inspections - 8
End Date Description Inspector Results Comments
08/03/2009 INSP - FULL RSPANGLE Approved 8.) TFC 102.4 OBTAIN C OF O TO COMPLY WITH IBC.
08/03/2009 INSP - FULL RSPANGLE Approved 7.) TFC 901.6.2 FIRE ALARM ANNUAL INSPECTION REPORT MUST BE SUBMITTED UPON RE-INSPECTION.
08/03/2009 INSP - FULL RSPANGLE Approved 6.) TFC 315.2 CLEAN LEAVES AND DEBRI FROM AROUND BOTH WATER HEATERS.
08/03/2009 INSP - FULL RSPANGLE Approved 5.) TFC 605.4 MULTI-PLUG ADAPTER IN TWO'S ROOM IS NOT PERMITTED.
08/03/2009 INSP - FULL RSPANGLE Approved 4.) TFC 605.4.2 POWER STRIPS IN OFFICE CANNOT BE PIGGY BACKED TOGETHER.
08/03/2009 INSP - FULL RSPANGLE Approved 3.) TFC 1008.1.8 EGRESS GATE FROM EAST SIDE ENCLOSURE MUST BE OPENABLE FROM EGRESS SIDE WITHOUT A KEY OR SPECIAL KNOWLEDGE.
08/03/2009 INSP - FULL RSPANGLE Approved 2.) TFC 1008.1.4 SLIDE BOLT ON EGRESS DOOR FROM BATHROOM IS NOT PERMITTED.
08/03/2009 INSP - FULL RSPANGLE Approved 1.) TFC 1008.1.9 MAIN EXIT DOORS MUST SWING IN DIRECTION OF TRAVEL AND NO LOCKS OR LATCHES EXCEPT PANIC HARDWARE.