Case: T09FR02522
Case Details
Entered Date:
07/29/2009
Applicant:
BUTLER MARGARET
Description:
Full Fire Prevention Inspection
Outstanding Inspections
Case Number: T09FR02522
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 07/29/2009 | VIOL - PRECAUTION AGAINST FIRE | DSIWARSKI | Violation | IFC.315.2.1 Remove top shelf of storage rack in storage room for proper clearance. |
| 07/29/2009 | VIOL - BUILDING SVCS & SYSTEMS | DSIWARSKI | Violation | IFC.605.1 Replace 'Blank' on electrical service panel on East side of building. Display address per Pima County address requirements. |
| 07/29/2009 | VIOL - FIRE RESIST.RATED CONST | DSIWARSKI | Violation | IFC.703.1 Repair on West side of building open wiring, cover/enclose. |
| 07/29/2009 | VIOL - FIRE PROTECTION SYSTEMS | DSIWARSKI | Violation | IFC.901.4.1 Fire alarm system requires annual inspection. Last inspection 6/7/2008. |