Case: T09FR02520
Case Details
Entered Date:
07/29/2009
Applicant:
1690 N STONE AVENUE OFFICE SUITES LLC
Description:
SELOF INSPECTION
Outstanding Inspections
Case Number: T09FR02520
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | " 1IFC 901.6: If you have a fire extinguisher in your building, has it been serviced within the past 12 months? Fire extinguishers shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed |
| 07/29/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | 1. IFC 605.3: Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated |
| 07/29/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | 2. IFC 315.2.1: Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. |
| 07/29/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | 2. IFC 605.5: Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances |
| 07/29/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | 3. IFC 605.6: Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |