Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/29/2009

Applicant:

CRESTWOOD HOSPITALITY LLC

Description:

Full Fire Prevention Inspection.

Outstanding Inspections

Case Number: T09FR02519
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
07/29/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request. _____1. Provide documentation of the sprinkler system inspection report for fire department records. _____2. Provide documentation of the fire alarm system inspection report for fire department records. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02519
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/27/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.