Case: T09FR02519
Case Details
Entered Date:
07/29/2009
Applicant:
CRESTWOOD HOSPITALITY LLC
Description:
Full Fire Prevention Inspection.
Outstanding Inspections
Case Number: T09FR02519
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/29/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request. _____1. Provide documentation of the sprinkler system inspection report for fire department records. _____2. Provide documentation of the fire alarm system inspection report for fire department records. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02519
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |