Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

07/29/2009

Applicant:

3100 LLC

Description:

self inspection

Outstanding Inspections

Case Number: T09FR02516
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
07/29/2009 INSP - SELF INSPECTION PROGRAM JDAVIS Correction Required 1. IFC 1008.1.8.3 #2.2: A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background
07/29/2009 INSP - SELF INSPECTION PROGRAM JDAVIS Correction Required 2. IFC 1011.2: Illumination. Exit signs shall be internally or externally illuminated.