Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

07/29/2009

Applicant:

BRIGGS JAMES E JR TR

Description:

SELF INSPECTION

Outstanding Inspections

Case Number: T09FR02505
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
07/29/2009 INSP - SELF INSPECTION PROGRAM JDAVIS Correction Required 1. IFC 605.3: Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated
07/29/2009 INSP - SELF INSPECTION PROGRAM JDAVIS Correction Required 2. IFC 315.2.1: Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.