Pepe and sons fire inspection.

Outstanding Inspections

Case Number: T09FR02451
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
07/27/2009 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146, Fax 791-5346.
07/27/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
07/27/2009 VIOL - FIRE RESIST.RATED CONST JLOYA Violation 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02451
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/11/2009 INSP - REINSPECTION JLOYA Approved Reinspection done 8-10-09 with all violations abated.