End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/21/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | 3. IFC 605.6: Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |
07/21/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | 1. IFC 605.3: Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated |