07/20/2009

Applicant:

EL RIO OB/GYN ASSOCIATES LLC

Description:

Full Fire Prevention Inspection

Outstanding Inspections

Case Number: T09FR02388
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
07/20/2009 VIOL - BUILDING SVCS & SYSTEMS RSPANGLE Violation TFC.605.3 A 30 inch working space must be provided in front of electrical breaker panel in cleaning supply closet.
07/20/2009 VIOL - BUILDING SVCS & SYSTEMS RSPANGLE Violation TFC.605.4 The multi-plug adapter in outlet in employee break room needs to be replaced with an approved UL/FM listed power strip with over current protection.
07/20/2009 VIOL - FIRE PROTECTION SYSTEMS RSPANGLE Violation TFC.901.6 The building sprinkler system is past due for annual inspection.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02388
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/16/2009 INSP - FULL RSPANGLE Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. SPRINKLER SYSTEM ANNUAL INSPECTONS REPORT WAS SUBMITTED. 5 YEAR CHECK VALVE INSP. DUE IN 2013. APPPROVED.