Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/16/2009

Applicant:

PRIMERO DIEZ INC

Description:

Full Fire Prevention Inspection

Outstanding Inspections

Case Number: T09FR02340
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
07/16/2009 VIOL - BUILDING SVCS & SYSTEMS DSIWARSKI Violation IFC.605.4 Multiplug adapters shall not eb used on East wall of shop area. ____ Remove multiplug adapter.
07/16/2009 VIOL - BUILDING SVCS & SYSTEMS DSIWARSKI Violation IFC.605.5 Extension cords shall not be substituted for permanent wiring of North wall of shop area. ____ Replace extension cord.
07/16/2009 VIOL - MEANS OF EGRESS DSIWARSKI Violation IFC.1008.1.8 Back egress door shall be readily openable from egress side without a key or special knowledge or effort. ____Remove multiple locks and latches from rear egress door.
07/16/2009 VIOL - MEANS OF EGRESS DSIWARSKI Violation IFC.1008.1.8.4 Manually operated flush bolts or surface bolts are not permitted. ____Remove surface bolts on rear door.