Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

07/14/2009

Applicant:

CITY SURF MANAGEMENT GROUP LLC

Description:

Inspection

Outstanding Inspections

Case Number: T09FR02273
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
07/14/2009 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 504.2 Sign shall be posted at south door near riser stating "This Door Blocked".
07/14/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 603.1 Metal chimney from water heater shall be repaired.
07/14/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Blocked panels
07/14/2009 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.4 Multiplug adapter.
07/14/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.2 / 1008.1.8.4 Surface bolt lock on south gate shall not be used.
07/14/2009 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1011.1 Exit sign is required at south door from SW dining area.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02273
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/14/2009 INSP - FULL TKNAPP Approved