Case: T09FR02234
Case Details
Entered Date:
07/08/2009
Applicant:
EL RIO SANTA CRUZ NEIGHBORHOOD HEALTH
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T09FR02234
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2009 | INSP - FULL | RSPANGLE | Violation | 1.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN EMPLOYEE LOUNGE. |
| 07/08/2009 | INSP - FULL | RSPANGLE | Violation | 2.) TFC 901.6.2 FIRE ALARM AND SPRINKLER SYSTEM ANNUAL INSPECTION REPORT MUST BE SUBMITTED UPON RE-INSPECTION. |