Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR02207
Case Details
Entered Date:
07/07/2009
Applicant:
MENLO PARK SHOPPING CENTER COMPANY
Description:
SPRINKLER COMOLAINT
Outstanding Inspections
Case Number: T09FR02207
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2009 | INSP - FULL | EDESCHAI | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A REVISED COPY OF THE INSPECTION REPORT TO BE FORWARDED TO THIS OFFICE 1) THE FIRE ALARM BELL IS NOT WORKING AND SHALL BE REPAIRED 2) STE. # 1219 - A SPRINKLER HEAD IS COVERED WITH DRY WALL SPRAY AND SHALL BE CHANGED OUT. IT IS BY THE EMPLOYEE REST ROOM 3) GUAGES AT THE RISER NEED TO BE CHANGED OUT OR CALIBRATED 4) THE RISER CHECK VALVE IS NOT FUNCTIONING PROPERLY 5) REPLACE CEILING TILES IN STE. # 1219 6) OUR RECORDS INDICATE THAT THE 5 YEAR INTERNAL INSPECTION IS DUE. |