Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/07/2009

Applicant:

MASONIC-SCOTTISH RITE CATHEDRAL ASSN

Description:

Scottish rite cathedral fire inspection.

Outstanding Inspections

Case Number: T09FR02202
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
07/07/2009 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146, Fax 791-5346.
07/07/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. ___Provide copy of last sprinkler system inspection report.
07/07/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment. ___ Provide copy of last hood inspection report.
07/07/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02202
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/22/2010 INSP - REINSPECTION JLOYA Approved Violations abated.