Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/02/2009

Applicant:

DND NEFFSON CO

Description:

Full Fire Prevention Inspection Building Rep: Enrique Castillio Phone # 887-0653

Outstanding Inspections

Case Number: T09FR02163
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
07/02/2009 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
07/02/2009 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. _____ Maintain proper working space around all electrical panels and equipment according to code. (Transformer)
07/02/2009 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag your hood system in order to meet code standards
07/02/2009 VIOL - MEANS OF EGRESS JLONGO Correction Required 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions hindering the use, the path, or the activity of the egress door and be sure to always maintain a clear and obstruction free path to your rear egress door.
07/02/2009 VIOL - COMPRESSED GASES JLONGO Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ___ ___ ___ ___________________ Passed on: ________ (Joseph P. Longo)