Description:

Mi Casita Tortilla factory fire inspection.

Outstanding Inspections

Case Number: T09FR02117
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
06/29/2009 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146, Fax 791-5346.
06/29/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 609.2 Where required, A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
06/29/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.1 Ventilation system. The ventilation system in connection with hoods shall be operated at the re-quired rate of air movement, and classified grease filters shall be in place when equipment under a kitchen grease hood is used.
06/29/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02117
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/29/2009 INSP - REINSPECTION JLOYA Approved All violations abated, appeal granted. citation was issued with owner pleading responsible to two charges.