Case: T09FR02067
Case Details
Entered Date:
06/26/2009
Applicant:
SAGUARO VISTA VENTURES LLC
Description:
Full, Inspector M. Pursley/G. D'Auria
Outstanding Inspections
Case Number: T09FR02067
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2009 | INSP - FULL | MPURSLEY | Correction Required | |
06/30/2009 | VIOL - FIRE RESIST.RATED CONST | MPURSLEY | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile |
06/30/2009 | VIOL - FIRE PROTECTION SYSTEMS | MPURSLEY | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained. |
06/30/2009 | VIOL - MEANS OF EGRESS | MPURSLEY | Correction Required | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the ---- egress door, as bolt lock of any kind are not permitted |
06/30/2009 | VIOL - DRY CLEANING | MPURSLEY | Correction Required | 1205.1.5 Equipment maintenance and housekeeping. Proper maintenance and operating practices shall be observed in order to prevent the leakage of solvent or the accumulation of lint. _____Keep lint accumulation cleaned regularly so build-up does not occur. ____Vent pipes on equipment with exhaust to outside. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02067
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/13/2009 | INSP - REINSPECTION | MPURSLEY | Approved |