Case: T09FR02019
Case Details
Entered Date:
06/22/2009
Applicant:
BEWS FAMILY LP (THE)
Description:
Full
Outstanding Inspections
Case Number: T09FR02019
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2009 | VIOL - PRECAUTION AGAINST FIRE | MPURSLEY | Correction Required | 315.2 Storage in buildings Storage of combustible materials shall be orderly. Storage shall be separated from heaters or heating devices so that ignition cannot occur. ____Keep hot water heater clear. |
06/22/2009 | VIOL - BUILDING SVCS & SYSTEMS | MPURSLEY | Correction Required | 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips. |
06/22/2009 | VIOL - MEANS OF EGRESS | MPURSLEY | Correction Required | 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, and/or replace the emergency lighting in order to meet code standards 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions and be sure to always maintain a clear and obstruction free path to your emergency exit. ****check on breaker locks**** |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02019
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2009 | COMPL - REINSPECTION | MPURSLEY | Approved |