Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/19/2009

Applicant:

SISTERS OF ST JOSEPH IN ARIZ

Description:

Suppercuts Helene Edwards 520-296-3967 Inspector M. Pursley

Outstanding Inspections

Case Number: T09FR02001
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
06/19/2009 INSP - FULL MPURSLEY Correction Required
06/19/2009 VIOL - MEANS OF EGRESS MPURSLEY Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the double-key lock and replace with an approved locking device such as, thumb turn lock or panic hardware 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____ Remove extra door knob on back door Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____________________ ___/___/___

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR02001
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/22/2009 INSP - REINSPECTION MPURSLEY Approved All corrections made 7/22/09