Case: T09FR02001
Case Details
Entered Date:
06/19/2009
Applicant:
SISTERS OF ST JOSEPH IN ARIZ
Description:
Suppercuts Helene Edwards 520-296-3967 Inspector M. Pursley
Outstanding Inspections
Case Number: T09FR02001
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2009 | INSP - FULL | MPURSLEY | Correction Required | |
06/19/2009 | VIOL - MEANS OF EGRESS | MPURSLEY | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the double-key lock and replace with an approved locking device such as, thumb turn lock or panic hardware 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____ Remove extra door knob on back door Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____________________ ___/___/___ |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR02001
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2009 | INSP - REINSPECTION | MPURSLEY | Approved | All corrections made 7/22/09 |