Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/16/2009

Applicant:

STARR PASS RESORT DEVELOPMENTS LLC

Description:

Starr Pass Club house fire inspection.

Outstanding Inspections

Case Number: T09FR01962
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
06/16/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
06/16/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
06/16/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
06/16/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non-required fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code
06/16/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request ___Provide copy of last sprinkler system inspection report.
06/16/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ___Remove sliding bolts fron emergency exit by womens locker.
06/16/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs
06/16/2009 VIOL - COMPRESSED GASES JLOYA Violation 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. ____ Secure containers, cylinders and tanks to a fixed object with one or more restraints

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01962
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
06/16/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146, Fax 791-5346.
10/05/2009 INSP - REINSPECTION JLOYA Approved All violations abated.