Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR01961
Case Details
Entered Date:
06/16/2009
Applicant:
SPRAY MASTER AUTO BODY & PAINT INC
Description:
Spray Masters fire inspection.
Outstanding Inspections
Case Number: T09FR01961
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2009 | INSP - FULL | JLOYA | Violation | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146, Fax 791-5346. |
06/16/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. |
06/16/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
06/16/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities. |
06/16/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. ___Provide copy of last sprinnkler system inspection report. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01961
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |