Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/11/2009

Applicant:

CHOICE PROPERTIES 43% INT ET AL

Description:

Full

Outstanding Inspections

Case Number: T09FR01925
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
VIOL - INT.FINISH, DEC. MATL'S None Not Inspected
06/11/2009 VIOL - PRECAUTION AGAINST FIRE MPURSLEY Correction Required 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code.
06/11/2009 VIOL - FIRE SERVICE FEATURES MPURSLEY Correction Required 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. ____Place address numbers over front main door.
06/11/2009 VIOL - BUILDING SVCS & SYSTEMS MPURSLEY Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used… Electrical blanks shall be placed in all open spaces within any electrical panel or box. _____ Place electrical blanks in any open void spaces in your electrical panel 605.4.1 Power tap design Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. _____Replace with approved multiple plug adapter. 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips.
06/11/2009 VIOL - FIRE PROTECTION SYSTEMS MPURSLEY Correction Required 807.1 General requirements Curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 806.2 or be noncombustible. _____ Remove or treat your curtains/draperies to make them properly fire rated. If they are treated the proper paper work must be shown to prove compliance.
06/11/2009 VIOL - FIRE PROTECTION SYSTEMS MPURSLEY Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag hood system.
06/11/2009 VIOL - MEANS OF EGRESS MPURSLEY Correction Required 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code _____Have exit signs repaired/replaced.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01925
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/24/2009 INSP - REINSPECTION MPURSLEY Approved