Full Fire Prevention Inspection.

Outstanding Inspections

Case Number: T09FR01919
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
06/10/2009 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required IFC 315.2.1 1. Remove the storage located above the walk in frig.
06/10/2009 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required IFC 505.1 1. Replace the mnissing address number on the building.
06/10/2009 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required IFC 703.1 1. Replace the missing ceiling tiles located in the kitchen.
06/10/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 1. Service and tag all portable fire extinguishers. 2. Service and tag the kitchen hood extinguishing system and correct any deficiencies noted during the inspection.
06/10/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 906.7 1. The portable fire extinguisher located in the kitchen by the back door shall be properly mounted.
06/10/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1011.2 1. Replace the burned-out bulb located in the south exit sign.
06/10/2009 VIOL - COMPRESSED GASES JBURGE Correction Required IFC 3003.5.3 1. Secure the CO2 cylinder located in the kitchen with one or more restraints to a fixed object.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01919
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/08/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.