Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/09/2009

Applicant:

CHOICE PROPERTIES 43% INT ET AL

Description:

Countrywide/Bank of America Suzana Luquez 520-731-8382 Inspector M. Purlsey

Outstanding Inspections

Case Number: T09FR01911
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
06/09/2009 INSP - FULL MPURSLEY Correction Required Initial inspection 6/9/09 Reinspection due 6/23/09
06/09/2009 VIOL - BUILDING SVCS & SYSTEMS MPURSLEY Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used… Electrical blanks shall be placed in all open spaces within any electrical panel or box. _____ Remove locks on breakers in your electrical panel
06/09/2009 VIOL - FIRE PROTECTION SYSTEMS MPURSLEY Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
06/09/2009 VIOL - MEANS OF EGRESS MPURSLEY Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, and/or replace the emergency lighting in order to meet code standards 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code _____Repair Exit signs. 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions and be sure to always maintain a clear and obstruction free path to your exit. 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. ____Place exit sign on back door(N.E.) exit. **** FDC in back of 6725 on North wall **** Property Mgr. 320-0010 Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____________________ ___/___/___

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01911
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/29/2009 INSP - REINSPECTION MPURSLEY Approved