Description:

Lowes fire inspection.

Outstanding Inspections

Case Number: T09FR01905
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
06/09/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ___Garden center.
06/09/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. ____Garden center, outside installers office, Handy car charger.
06/09/2009 VIOL - FIRE RESIST.RATED CONST JLOYA Violation 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ____ Repair holes in ceiling. (training room)
06/09/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. ___Provide copy of sprinkler system last inspection report.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01905
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
06/09/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146, Fax 791-5346.
06/24/2009 INSP - REINSPECTION JLOYA Approved All violations abated.