Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/08/2009

Applicant:

HD BROADWAY LLC

Description:

Home Depot Goerge Smedley 520-722-6171 Inspector Purlsey/Cobb

Outstanding Inspections

Case Number: T09FR01889
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
06/08/2009 INSP - FULL MPURSLEY Correction Required Initial inspection 6/5/09 Reinspection due 6/19/09
06/08/2009 VIOL - PRECAUTION AGAINST FIRE MPURSLEY Correction Required 313.1 General. Fueled equipment, including but not limited to motorcycles, mopeds, lawn-care equipment and portable cooking equipment, shall not be stored, operated or repaired within a building. ____Remove fuel from rental equipment that is stored in doors. **** Fuel and Remove fuel Outside only **** 315.2.3 Equipment rooms Combustible materials shall not be stored in boiler rooms, mechanical rooms, or electrical equipment rooms. ____Keep all combustibles out of electrical room.
06/08/2009 VIOL - FIRE SERVICE FEATURES MPURSLEY Correction Required 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. ____Keep all stand pipes clear
06/08/2009 VIOL - BUILDING SVCS & SYSTEMS MPURSLEY Correction Required 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. _____ Maintain proper working space around all electrical panels according to code. 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording _____Label inside door of electrical room. 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Repair electrical conduit
06/08/2009 VIOL - FIRE PROTECTION SYSTEMS MPURSLEY Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag all portable fire extinguishers in order to meet code standards 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). _____Mount all fire extinguishers
06/08/2009 VIOL - MEANS OF EGRESS MPURSLEY Correction Required 1011.1 Where required An approved exit sign shall mark exits and exit access doors and be readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs, in cases where the exit or the path of egress travel is not immediately visible to the occupants; Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. _____Place exit signage so that it is visible from the end of isles. 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. _____Keep exit pathways clear. ____Place sign on register gates stating, "EMERGENCY EXIT" and "push to open" ____Show proof that security device breaks away with less than 15lbs. of force. _____Repair emegency exits in guarden area.
06/08/2009 VIOL - COMPRESSED GASES MPURSLEY Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times
06/08/2009 VIOL - FLAMMABLE LIQUIDS MPURSLEY Correction Required 3404.3.2 Liquid storage cabinets. Where other sections of this code require that liquid containers be stored in storage cabinets, such cabinets and storage shall be in accordance with Sections 3404.3.2.1 through 3404.3.2.3. ____Repair handle on flammable liquids cabinet. ____Place seal on door to reduce gasoline fumes. 3404.3.4 Quantity limits for storage. Liquid storage quantity limitations shall comply with Sections 3404.3.4.1 through 3404.3.4.4. ____All fuel cans must be kept in flammable liquids cabinet. ____Place seal on parts washer drain when not in use. Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____________________

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01889
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/07/2009 INSP - REINSPECTION MPURSLEY Approved