Description:

Full Fire Prevention Inspection. Alejandre Maldonado 622-0210

Outstanding Inspections

Case Number: T09FR01881
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
06/05/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1. Service and tag the portable fire extinguisher used to extinguish the microwave fire. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
06/05/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. _____1. The deficiencies noted on the last hood system inspection reports shall be corrected. NOTE: See attached reports.
06/05/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. Clean and remove all grease accumulation from the kitchen hood systems and provide documentation of the cleanings.
06/05/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Repair the East door located by the fryers and remove the locking hasp. NOTE: The door will not open.
06/05/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: _____1. Both northwest EXIT signs shall have emergency back-up power.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01881
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/06/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.