Case: T09FR01880
Case Details
Entered Date:
06/05/2009
Applicant:
SALAZAR JOSE LUIS & MARIA JESUS JT/RS
Description:
Full Fire Prevention Inspection. Martina Egurrola 884-1629
Outstanding Inspections
Case Number: T09FR01880
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2009 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1. Remove all extension cords used for permanent electrical wiring. NOTE: Replace the extension cords with fused multi-plug adapters plugged directly into an electrical outlet. |
| 06/05/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. Clean and remove all grease accumulation from the kitchen hood system and provide documentation of the cleaning. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 06/05/2009 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. _____1. the Class K portable fire extinguisher shall be mounted. |
| 06/05/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the double keyed lock from the North door in the kitchen. NOTE: Replace the double keyed lock with a thumb-turn lock. _____2. Remove the double keyed lock from the East door located in the dinning area. NOTE: Replace the double keyed lock with a thumb-turn lock. |
| 06/05/2009 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. _____1. Post the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" above the inside of the main entrance door. |
| 06/05/2009 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. _____1. Secure the C02 cylinders located in the kitchen to prevent them from falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01880
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2009 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |