Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/02/2009

Applicant:

PIZZA HUT OF ARIZONA

Description:

Pizza Hut fire inspection.

Outstanding Inspections

Case Number: T09FR01846
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
06/02/2009 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146, Fax 791-5346
06/02/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels
06/02/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. __Remove locking bolt from rear emergency exit by kitchen.
06/02/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1014.4.1 - Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches. Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches in width.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01846
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/17/2009 INSP - REINSPECTION JLOYA Approved All violations abated.