Case: T09FR01806
Case Details
Entered Date:
05/28/2009
Applicant:
JONES HALVAN L & RETTA TRUSTEES
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T09FR01806
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2009 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.1 PLACE A SIGN IN BREAK ROOM TO UNPLUG TOASTER WHEN DONE USING REPLACE MISSING OUTLET COVERS IN THE CHROMIRA ROOM |
| 05/28/2009 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.4 REMOVE THE MULTIPLUG ADAPTER UNDER COUNTER IN THE QUICK BOOKS SERVER ROOM AND REPLACE WITH A FUSED POWER STRIP |
| 05/28/2009 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1008.1.8.4 REMOVE THE DOUBLED KEYLOCKS IN TERI'S OFFICE AND IN THE OLD MAINTENANCE ROOM. REPLACE WITH A THUMB TURN LOCK |
| 05/28/2009 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1027.3 REPAIR THE 2 EXIT SIGNS IN MAIN HALL |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01806
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2009 | INSP - FULL | MWAINWRI | Approved |