Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/28/2009

Applicant:

OSTROY IRVING & SHIRLEY UND 25% INT

Description:

Full Fire Prevention Inspection. Mark Demming 326-2600

Outstanding Inspections

Case Number: T09FR01804
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
05/28/2009 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required IFC 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. _____1. Address numbers shall be in accordance with Pima County address display requirements. See attached form.
05/28/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. _____1. Align the hood extinguishing system nozzles to properly cover the fryers.
05/28/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). **Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. _____1. The west exit door shall not require more than 15 pounds of force to open. _____2. Remove the double-keyed locks from the two doors that lead to the patio. _____3. The two doors that lead to the patio shall have panic hardware installed as the opening device.
05/28/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. Repair the EXIT sign located above the main entrance. _____2. Repair the EXIT sign located above the west exit door.
05/28/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1028.8 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. _____1. Remove the padlocks and locking hasps from the exit doors located in the patio.
05/28/2009 VIOL - COMPRESSED GASES JBURGE Correction Required IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: *** Securing containers, cylinders and tanks to a fixed object with one or more restraints. _____1. Properly secure the compressed gas cylinders located by the southeast exit door. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01804
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/11/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been abated.