Case: T09FR01767
Case Details
Entered Date:
05/21/2009
Applicant:
CAMPBELL AVENUE SHOPPING CENTER LLC
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T09FR01767
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2009 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 901.6 HOOD SYSTEM IS DUE FOR INSPECTION K CLASS EXTINGUISHER NEEDS RECHARGING |
05/21/2009 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 901.6 THERE IS NO SPRINKLER COVERAGE IN THE BATHROOM HALLWAY. CONTACT A SPRINLER COMPANY TO HAVE A HEAD INSTALLED. |
05/21/2009 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1007.3 REPAIR EXIT SIGN AT FRONT ENTRANCE REPAIR EXIT SIGN AT REAR OF KITCHEN |
05/21/2009 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1027.5 REPAIR EMERGENCY LIGHT IN DINING AREA |
05/21/2009 | VIOL - COMPRESSED GASES | MWAINWRI | Violation | 2006 IFC 3005.6 SECURE COMPRESSED GAS BOTTLE IN CORNER. ONE BOTTLE IS SECURED WITH CHAIN THE OTHER IS NOT |
05/21/2009 | VIOL - LIQUID PETROLEUM GASES | MWAINWRI | Violation | 2006 IFC 3809.4 REMOVE PROPANE BOTTLE IN THE OFFICE |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01767
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/13/2010 | INSP - FULL | MWAINWRI | Approved |