Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/21/2009

Applicant:

CAMPBELL AVENUE SHOPPING CENTER LLC

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T09FR01767
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
05/21/2009 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 HOOD SYSTEM IS DUE FOR INSPECTION K CLASS EXTINGUISHER NEEDS RECHARGING
05/21/2009 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 THERE IS NO SPRINKLER COVERAGE IN THE BATHROOM HALLWAY. CONTACT A SPRINLER COMPANY TO HAVE A HEAD INSTALLED.
05/21/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1007.3 REPAIR EXIT SIGN AT FRONT ENTRANCE REPAIR EXIT SIGN AT REAR OF KITCHEN
05/21/2009 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.5 REPAIR EMERGENCY LIGHT IN DINING AREA
05/21/2009 VIOL - COMPRESSED GASES MWAINWRI Violation 2006 IFC 3005.6 SECURE COMPRESSED GAS BOTTLE IN CORNER. ONE BOTTLE IS SECURED WITH CHAIN THE OTHER IS NOT
05/21/2009 VIOL - LIQUID PETROLEUM GASES MWAINWRI Violation 2006 IFC 3809.4 REMOVE PROPANE BOTTLE IN THE OFFICE

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01767
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/13/2010 INSP - FULL MWAINWRI Approved