Entered Date:
05/18/2009
Applicant:
ALVERNON PLACE LLC
Description:
self inspection
Outstanding Inspections
Case Number: T09FR01728
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | " 1IFC 901.6: If you have a fire extinguisher in your building, has it been serviced within the past 12 months? Fire extinguishers shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed |
| 05/18/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | " 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. |
| 05/18/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | 1. 1IFC 901.6: If you have a sprinkler system in your building, has it been tested and serviced within the past 12 months? Alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. |
| 05/18/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | 1. IFC 605.3: Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated |
| 05/18/2009 | INSP - SELF INSPECTION PROGRAM | JDAVIS | Correction Required | 3. IFC 605.6: Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |