Case: T09FR01708
Case Details
Entered Date:
05/15/2009
Applicant:
BROADWAY POWERCENTER GROUP LLC
Description:
Verizon Albert Quijada 520-886-1691 Inspector M. Pursley
Outstanding Inspections
Case Number: T09FR01708
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2009 | INSP - FULL | MPURSLEY | Correction Required | Initial inspection 5/15/09 Reinspection due 5/29/09 |
05/15/2009 | VIOL - FIRE RESIST.RATED CONST | MPURSLEY | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile |
05/15/2009 | VIOL - COMPRESSED GASES | MPURSLEY | Correction Required | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____________________ ___/___/___ |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01708
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2009 | COMPL - REINSPECTION | MPURSLEY | Approved |