Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/12/2009

Applicant:

H L F PROPERTIES INC

Description:

Full Fire Prevention Inspection

Outstanding Inspections

Case Number: T09FR01632
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
05/12/2009 VIOL - PRECAUTION AGAINST FIRE DSIWARSKI Revision No violation noted in Chapter 3
05/12/2009 VIOL - BUILDING SVCS & SYSTEMS DSIWARSKI Violation IFC.605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ____Extension cord in Back Area of Clinic must be not be used as permanent wireing and must be removed.
05/12/2009 VIOL - FIRE PROTECTION SYSTEMS DSIWARSKI Violation IFC.906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Fire Extinguisher in Back Room of Clinic must be serviced/maintained.
05/12/2009 VIOL - MEANS OF EGRESS DSIWARSKI Violation IFC.1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background... ____ Sign required on egress door: "THIS DOOR IS TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED". IFC.1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ____Remove multiple locks on rear door.
05/12/2009 VIOL - COMPRESSED GASES DSIWARSKI Violation 3003.5.3 Securing compressed gas containers, cylinders and tanks. Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. ____ Secure oxygen cylinder in Operating Room.