Case: T09FR01598
Case Details
Entered Date:
05/12/2009
Applicant:
DND NEFFSON CO
Description:
Full Fire Prevention Inspection Building Rep: Mona Roberts Phone # 293-1506
Outstanding Inspections
Case Number: T09FR01598
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2009 | INSP - FULL | JLONGO | Correction Required | Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
05/12/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLONGO | Correction Required | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Electrical blanks shall be placed in all open spaces within any electrical panel or box. _____ Remove the breaker inhibiters from your electrical box as they prevent the box from breaking properly and are deemed an electrical hazard 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Place approved cover(s) over the electrical outlet (Break room) |
05/12/2009 | VIOL - FIRE RESIST.RATED CONST | JLONGO | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile (Quiet room) _____ Fix, repair, or restore all openings or holes in the fire resistive walls (Camera room, Top stock) |
05/12/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLONGO | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag all portable fire extinguishers in order to meet code standards (Break room, Camera room) 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ Properly hang all portable fire extinguishers according to code (Cash wrap B) |
05/12/2009 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code _____ Fix, repair, and/or replace all non-working exit signs in order to meet code standards (Back up power) ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ ___________________ Passed on: ________ (Joseph P. Longo) |