Outstanding Inspections

Case Number: T09FR01591
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
05/11/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____1. Remove the unfused multiplug adapter located in the office.
05/11/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Replace the missing electrical outlet cover located in the maintenance room. _____2. Replace the missing light switch cover located in the maintenance room.
05/11/2009 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. _____1. Replace the missing ceiling tile located in the maintenance room. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
05/11/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1. The kitchen hood extinguishing system shall be serviced and shall pass the hydrostatic test or shall be upgraded to a UL 300 system.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01591
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/29/2009 INSP - FULL JBURGE Approved Carl Schultz is handling the hood system installation approval. Case Closed.