Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/11/2009

Applicant:

DND NEFFSON CO

Description:

Full Fire Prevention Inspection Building Rep: Cristina Hernandez Phone # 520-292-0696

Outstanding Inspections

Case Number: T09FR01585
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
05/11/2009 INSP - FULL JLONGO Correction Required Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations.
05/11/2009 VIOL - PRECAUTION AGAINST FIRE JLONGO Correction Required 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain the proper ceiling clearance around your sprinkler heads according to code.
05/11/2009 VIOL - BUILDING SVCS & SYSTEMS JLONGO Correction Required 605.4 Multi-plug adapters Multi-plug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC electrical code shall be prohibited. _____ All Multi-plug adapters shall be removed and/or replace with approved fused power strips. 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Electrical blanks shall be placed in all open spaces within any electrical panel or box. _____ Remove the breaker inhibiters from your electrical box as they prevent the box from breaking properly and are deemed an electrical hazard.
05/11/2009 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ properly hang all portable fire extinguishers according to code
05/11/2009 VIOL - MEANS OF EGRESS JLONGO Correction Required 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions hindering the use, the path, or the activity of the egress door and be sure to always maintain a clear and obstruction free path to your rear egress door. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____ ___________________ Passed on: ________ (Joseph P. Longo)