Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/08/2009

Applicant:

STARWOOD TUCSON REALTY LLC

Description:

Four Points Sheraton Steve Connelly 520-319-4250 Inspector J. Nagore/M. Pursley

Outstanding Inspections

Case Number: T09FR01574
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
05/08/2009 INSP - FULL MPURSLEY Correction Required ***waiting on sprinkler report results***
05/08/2009 VIOL - ADMINISTRATION MPURSLEY Correction Required 110.1.1 Unsafe conditions. Structures or existing equipment that are or hereafter become unsafe or deficient because of inadequate means of egress or which constitute a fire hazard, or are otherwise dangerous to human life or the public welfare, or which involve illegal or improper occupancy or inadequate maintenance, shall be deemed an unsafe condition. ____Cap open gas line.
05/08/2009 VIOL - PRECAUTION AGAINST FIRE MPURSLEY Correction Required 315.2.3 Equipment rooms Combustible materials shall not be stored in boiler rooms, mechanical rooms, or electrical equipment rooms. ____remove combustibles form HWH room. 316.2 Clothes dryers. Clothes dryers shall be frequently cleaned to maintain the lint trap and mechanical and heating components free from excessive accumulations of lint. ____have lint catcher and underground parking cleaned of lint build up.
05/08/2009 VIOL - BUILDING SVCS & SYSTEMS MPURSLEY Correction Required 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters. 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips. 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Place approved cover(s) over the electrical panels and open junction boxes. ***keep generator log up to date***
05/08/2009 VIOL - FIRE RESIST.RATED CONST MPURSLEY Correction Required 703.1 Maintenance The required fire-resistance-rated construction shall be maintained. Such elements shall be repaired, restored, or replaced when damaged, altered, breached, or penetrated. _____ Fix, repair, or restore all openings or holes in the fire resistive walls or ceiling.
05/08/2009 VIOL - FIRE PROTECTION SYSTEMS MPURSLEY Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _________________Hood system in conference kitchen is no longer in use and there will be no cooking appliance installed until system is up to date with code requirements. ____Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed 907.2.10.1.1 Group R-1. Single- or multiple-station smoke alarms shall be installed in all of the following locations in Group R-1: 1. In sleeping areas. 2. In every room in the path of the means of egress from the sleeping area to the door leading from the sleeping unit. 3. In each story within the sleeping unit, including basements. For sleeping units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level. _______________All smoke detectors are in place and have been tested.
05/08/2009 VIOL - MEANS OF EGRESS MPURSLEY Correction Required 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code _________________All exit signs have been tested and are up to code. 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. ______________All emergency lighting is in place tested and up to code.
05/08/2009 VIOL - COMPRESSED GASES MPURSLEY Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions. Thank you.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01574
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/08/2009 INSP - REINSPECTION MPURSLEY Approved Received sprinkler report today, all corrections made 7/8/09.