Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T09FR01567
Case Details
Entered Date:
05/06/2009
Applicant:
MIDVALE MARKETPLACE LLC
Description:
Chili's Fire inspection.
Outstanding Inspections
Case Number: T09FR01567
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/06/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. |
05/06/2009 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
05/06/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code. |
05/06/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. |
05/06/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01567
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/06/2009 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146 |
05/26/2009 | INSP - REINSPECTION | JLOYA | Approved | All violations abated |