Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/06/2009

Applicant:

DND NEFFSON CO

Description:

Full Fire Prevention Inspection. Kristi Caton 293-4074

Outstanding Inspections

Case Number: T09FR01561
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
05/06/2009 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required IFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. _____1. The storage located above the restroom shall be lowered to 18 inches below the sprinkler heads. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
05/06/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove all storage from obstructing the electrical service equipment located in the back room.
05/06/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____1. Service and tag the portable fire extinguisher located in the back room.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01561
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/27/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.