Description:

Full Fire Prevention Inspection. Ally Gracia 888-0336

Outstanding Inspections

Case Number: T09FR01559
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
05/06/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____1. Remove the tape from the eletrical breakers switches located in the back room. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
05/06/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove all storage from obstructing the electrical service equipment located in the back room.
05/06/2009 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. _____1. Replace the missing ceiling tiles located in the dressing room. _____2. Replace the missing ceiling tiles located in the stock room.
05/06/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. All EXIT signs shall be fully illuminated and shall work properly under emergency illumination conditions. -

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01559
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/27/2009 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.